0,27 $ netto
SinusPRO-800E device combines the functionality of a DC / AC (12 V), UPS, voltage regulator and battery charger. The rated power is 500 W and the maximum charging current is 10 A. The product uses a toroidal transformer ensuring higher efficiency and energy efficiency than structures based on transformers with E-cores. The inverter quickly switches from mains power to UPS, thanks to which the connected equipment can work without interference. An additional advantage is the LCD display informing about the current working status.
The inverter produces an alternating voltage with a sinusoidal wave, identical to that in the power grid. Thanks to this, it is possible to power devices equipped with electric motors and transformers, such as electric tools, pumps and low-power household appliances. There is no risk of damaging the powered equipment, which occurs when using inverters with a square wave voltage.
The most important features:
- DC / AC inverter (12 V);
- UPS backup power supply;
- voltage regulator and battery charger;
- rated power 500 W;
- instantaneous (overload) power 800 VA;
- charging current 10 A;
- sine wave output voltage.
Specification
sinusPRO 800E | |
Rated power (continuous) | 500 W |
Overload power (instantaneous) | 800 VA |
Battery voltage | 12 V |
Rectifier (charging current) | 10 A |
Automatic mains voltage regulator (AVR) | 140 - 275 V AC |
Current consumption without load | 0,3 - 1,5 A |
Admissible range of supply voltage | Switching to battery operation takes place when the mains voltage is lower than 160 V (± 5 V) or higher than 260 V (± 5 V) |
Supply voltage frequency | 45 - 65 Hz |
The frequency of the UPS output voltage | 50 Hz (± 0,5 Hz) |
Output voltage range |
Mains voltage regulator AVR: 204 - 240 V UPS (battery): 230 V (± 3%) |
Overload protection (battery powered) | In the event of an overload of 110% - 130%, the power is disconnected after 30 seconds. If the overload is greater than 130%, disconnection occurs immediately. |
Overload protection (mains supply) | The device warns of an overload until the fuses blown. |
Permissible humidity | 10%-90% RH |
Permissible working temperature | From 0 to 40 °C |
Dimensions | 230x145x180 mm |
Weight | 6,5 kg |