1,10 zł netto
The NDR-480-48 is a power supply from the popular company Mean Well, intended for mounting on a DIN TS-35 / 7.5 or TS-35/15 rail. The device is distinguished by a small housing (it is narrower than in other power supplies for a DIN rail) and high efficiency - 92.5%. Thanks to the wide input voltage range (90 - 264 V AC / 127 - 370 V DC) it is universal and can be used in many applications.
The output voltage is 48 V and the current is 10 A, which gives 480 W of power. The power supply has overvoltage, overload and overvoltage protection and protection against too high temperature. It is cooled passively, so it does not generate additional noise during operation. It has an active PFC circuit that is used to improve the power factor.
The most important features:
- 48 V output voltage;
- output current 10 A;
- 480 W output power;
- mounting on DIN TS-35 / 7.5 or TS-35/15 rail;
- overvoltage, overload, overvoltage and excess temperature protection;
- active PFC system.
Specification
NDR-480-48 | |
Output | |
---|---|
Voltage | 48 V DC |
Current | 10 A |
Current range | 0 ~ 10 A |
Power | 480 W |
Ripple & Noise | 150 mVp-p |
Voltage range | 48 ~ 55 V DC |
Voltage tolerance | ± 1% |
Stabilization from the electrical grid | ± 0,5% |
Stabilization from load changes | ± 1% |
Set / rise / hold time |
1500 ms / 100 ms / 16 ms at 230 V AC 3000 ms / 100 ms / 16 ms at 115 V AC |
Input | |
Voltage range |
90 - 264 V AC 127 - 370 V DC |
Frequency range | 47 - 63 Hz |
Efficiency | 92,5% |
AC current |
4,8 A at 115 V AC 2,4 A at 230 V AC |
Inrush current |
20 A przy 115 V AC 35 A przy 230 V AC |
Leakage current | < 2 mA / 240 V AC |
Protections | |
Overload | 105% - 130% output power |
Overvoltage |
56 - 65 V The device switches off when the voltage is too high |
Overheat | The device stops working until the temperature reduce |
Others | |
Permissible working temperature | From -20 to 70 °C |
Permissible air humidity during working | 20%-95% RH non-condensing |
Permissible storage temperature | From -40 to 85 °C |
Permissible air humidity during storage | 10%-95% RH |
Safety / Certificates |
UL508, TUV EN60950-1 I/P-O/P: 3K V AC, I/P-FG: 2K V AC, O/P-FG: 0,5K EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3 EN6100-4-2,3,4,5,6,8,11 EN55024 EN61000-6-2 (EN50082-2) EN61024-3 |
Dimensions | 85,5 x 125,2 x 128,5 mm |
Weight | 1,5 kg |