A small rectifier (power supply) dedicated to small and medium-sized telecommunications applications. The device offers high efficiency, reliability and protection of the output with the OR-ING diode, it is closed in a housing with a depth of 210 mm. The rectifier is installed in the power supply unit together with the Smartpack 2 controller. Suitable for applications requiring 2 to 3 kW, requires minimal work space, and has low heat emission.
The most important features:
- small and short housing;
- power density up to 26 W / CU IN;
- high performance;
- protection of the output with the OR-ING diode;
- hot-plug technology;
- coding modules with different voltages and powers.
Specification:
Flatpack S 48/1000 HE | |
Input parameters | |
---|---|
Voltage range (nominal) | 185 - 270 VAC |
Voltage range (maximum) | 85 - 300 VAC |
Frequency | 45 - 66 Hz |
Maximum current, at nominal input and full load | 5,9 Arms |
Power factor | > 0.99 at 50% or greater load |
Protections |
Fuse Shutdown above 305 VAC |
Output parameters | |
Nominal voltage | 53,5 VDC |
Voltage range | 43,5 - 57,6 VDC |
Maximum power | 1000 W |
Power at 85 VAC | 440 W |
Maximum current, at nominal input and full load | 20,9 A (at 48 VDC) |
Current split (Load 10% - 100%) | ±5% of the maximum current for a load from 10% to 100% |
Static voltage regulation (10% - 100% load) | ±0,5% |
Dynamic voltage regulation | ± 5.0% for 10-90% or 90-10% load changes, regulation time <50ms |
Back-up time, full load | > 20ms, output voltage> 41 VDC |
Noise | <150mV ptp, bandwidth 30Mhz |
Protections |
OR-ING diode short circuit protection protection against high temperature |
Others | |
Efficiency at 95.5% nominal voltage | 95,5%, > 95% at 40 - 100% load |
Insulation |
3.0 kVAC - input and output 1.5 kVAC - input and ground 710 VDC - output and ground |
Alarms, red LED on | Shutdown: from low supply voltage, high or low temperature, high output voltage. Damage to: rectifier, fan or CAN communication bus; low voltage alarm. |
Warning: yellow LED on | Rectifier in power limitation, battery current limit active, input voltage out of range, blinking on overvoltage shutdown. |
Green LED on | Normal mode (module working, no problems) |
Noise | < 46 dBA at nominal voltage and full load |
MTBF (Telcordia SR-332 Edition I method III (a)) | > 350000 (at ambient temperature : 25 °C) |
Working temperature |
From -40 to 85 °C, permissible humidity 5% -95% RH non-condensing |
Storage temperature | From -40 to 85 ° C. acceptable humidity 0% -99% RH non-condensing |
Dimensions / weight |
72x41,5x210 mm < 1 kg |
Standards | |
Electrical safety | UL 60950-1 3 editon, EN 60950-1 3 edition |
EMC |
ETSI EN 300 386 V.1.4.1 EN 61000-6-1 / -2 / -3 / -4 / -5 FCC part15 Subsection109 |
Environmental |
ETSI EN 300 019: 2-1 (class 1,2), 2-2 (class 2,3), 2-3 (Class 3,2) Compatible with ROHS |