-
0,26 € netto
An additional module (rectifier) for the Flatpack2 gym, with a power of 1800 W. The device is adapted to work with systems of various sizes, thanks to digital communication with Smartpack, its implementation has been simplified and flexibility has been increased. The 23" rack can accommodate 5 products, while the 19" rack can accommodate 4. The device can be used for: wireless, fiber optic and fixed telephony; access and broadband systems.
The most important features:
- high efficiency while maintaining a small size;
- digital control;
- cooling;
- unique "plug-and-play" connection;
- global approvals: CE, UL and NEBS certified.
Specification:
Prostownik Flatpack2 48/1800 | |
Input parameters | |
---|---|
Voltage | 85 - 290 V AC (nominal 185 - 275 V AC) |
Frequency | 45 - 66 Hz |
Maximum current | 10,7 A rms maximum for nominal input voltage and full load |
Power factor | > 0,99 at a load of 20% or more |
Protections |
fuse on both lines disconnection above 290 V AC |
Output parameters | |
Voltage | 53.5 V DC (control range): 43.5 - 56 V DC) |
Power | 1800 W at nominal input voltage |
Maximum current | 37,5 Amps at 48V DC and nominal input voltage |
Split current | ±3% |
Static voltage regulation | ±0,5% at load 10% - 100% |
Dynamic voltage regulation | ±5,0% for 10-90% or 90-10% load changes, control time <50 ms |
Backup time | > 20 ms; output voltage> 43.5 V DC with a load of 1500 W |
Interference and noise |
< 100 mV ptp 30 MHz bandwidth < 0,96 mV rms psophometric |
Protections |
Overload shutdown blocking diode short circuit protection high temperature protection |
Other | |
Efficiency | 92%, minimum 91% at load 40-90% |
Insulation |
3.0 kV AC - input and output 1.5 kV AC - input and ground 0.5 kV DC - output and ground |
Alarms |
Low power shutdown high temperature shutdown damage to the charger shutdown at output overvoltage fan error low voltage (43.5 V) CAN bus error |
Warnings |
Rectifier in power limitation battery current limit active too high voltage flickering when overvoltage cut-off no communication with CAN |
LED signaling |
Green LED: the device works, no problems Yellow LED: rectifier warning Red LED: rectifier error |
Working temperature | From -40 to 70 °C |
Storage temperature | From -40 to 85 °C |
Cooling | active, 2 fans (airflow from front to back) |
Fan speed | Regulated by temperature and load |
MTBF | >250,000 hours Telecordia SR-332 1st Edition Method III (a) |
Noise level | <50 dBA at nominal voltage and 70% load (ambient temperature <30 ° C) |
Permissible humidity |
Operation: 5% - 95% RH non-condensing Storage: 0% - 99% RH non-condensing |
Dimensions | 109x41,5x327 mm |
Weight | 1,8 kg |
Standards | |
Electrical safety |
IEC 60950-1 UL 60950-1 CSA 22,2 |
EMC |
ETSI EN 300 386 V.1.3.2 EN 61000-6-4 EN 61000-6-3 EN 61000-6-2 EN 61000-6-1 Telcordia NEBS GR1089 CORE |
Harmonics | EN 61000-3-2 |
Environmental |
ETSI EN 300 019-2 ETSI EN 300 132-2 Telcordia NEBDS GR63 CORE Zone 4 RoHS Compliance (Pending) |